This article provides notes on how to use PDO mappings other than the default 2nd PDO Mapping for Yaskawa SGDXS Series EtherCAT Drives.
The following table shows the default PDO mapping of the SERVOPACK, where the Default 2nd PDO Mapping is defined in the EtherCAT slave information file (XML).

Sync Manager PDO Assignment (1C10h to 1C13h) defines which PDOs are transferred during data communication.

Open Yaskawa’s Servo Drive configuration tool, SigmaWin+, and connect to the Servo Drive. Click Basic Function > Edit Parameters.

Next, open the EtherCAT parameter screen.

To disable the assignment between Sync Manager and PDOs, set subindex 0 of objects 1C12h to 1C13h to 0.

Set all mapping entries for the PDO mapping objects (1600h to 1603h, 1A00h to 1A03h).

Since a Delta Motion EtherCAT module was used in this article, check the Assigned checkboxes for 1st Transmit PDO Mapping and 1st Receive PDO Mapping in PDO Mapping.

Next, download the EtherCAT Configuration to the CPU.

Done! Successfully established EtherCAT communication with Yaskawa’s SGDXS series.

Data such as Modes of operation display was successfully retrieved.