EXOR#Part16_Let’s try using Modbus TCP Client

This article describes the steps from scratch to setting up a Modbus TCP Server using Node-Red on a SeeedStudio reComputer R1025-10 and using EXOR’s JMobile to access data with the Modbus TCP Client.

Let’s enjoy FA.

Reference Link

http://soup01.com/en/category/exor/

Implementation

SeeedStudio Side

Let’s start from  SeeedStudio’s reComputer R1025-10 edge device side first.

Install Node-red

Install Node-Red, referring to Node-Red from this Link or the official Node-Red website.

Raspberrypi#Install Node-Red

Install Modbus Node

We will implement a Modbus TCP Server using this Node in Node-Red.

node-red-contrib-modbus

Click on the Menu icon to the right of Node-Red>Manage Palette.

Search for node-red-contrib-modbus in the Install tab and install the appropriate Node.

Done!Modbus Node is now installed.

Add Modbus TCP Server

Drop Modbus>Modbus-Server into Flow.

Done!That’s all it took to get the Modbus Server up and running.

Configure Modbus TCP Server

Double-click on the Modbus Server Node you have just added.

This is the Modbus Server Node configuration screen.

Host Name

The Host name can be set to 0.0.0.0.

Port

Port allows you to set the Port used by the Modbus Server.

Register

The number of Modbus Server registers can be set in the red box. In the example below,

  • Coils: 1
  • Holdings: 400
  • Inputs: 400
  • Discrete: 1

Deloy

Finally, click Deploy to download the Flow.

EXOR Side

Next, set the EXOR side. This time, ex707M is used.

Add Protocols

Start JMobile and create a new project.

Select Modbus TCP from the drop-list.

Configure Modbus TCP Client

The Modbus TCP Client configuration screen appears.

PLC Network

Enable the PLC Network function. Using it, you can set up several Modbus TCP Servers with one Communication Driver.

Click Add to create a new Modbus Client.

This is the Modbus TCP Client configuration screen.

IP address

The IP address should be matched to the SeeedStudio reComputer R1025-10 side.

Port

The Port should match the Node-Red setting of SeeedStudio’s reComputer R1025-10.

 

Write Register Function

You can set the Function Code to be used when Holding Register and Write Coils (i.e. writing to registers).

PLC Model

PLC ModelはModbus Server側に合わせてください。今回はNode-Redのnode-red-contrib-modbusを使用するので、Generic Modbus(0‐Based)に設定してください。

Add Tags

Next, we will add some Tags.

This is the Tag setting screen.

Select the Protocol you just added and click >+.

When building the Protocol, we set the PLC Network mode, so select the appropriate Modbus Server on the Slave Id screen.

This Tag allows the Modbus TCP Server to read and write Holding Registers from 40000 to 100.

In addition, each Tag can be set to an update cycle according to the application.

Screen

Finally, create a simple screen and check the results.

Download

Download the project to ex707M using Run>Downlaod to Target.

Result

Done!Modbus TCP Server was successfully accessed.